|
Designing a 1600kVA/35kVA, 50Hz Distribution Oil
Transformer
General Information
Technical Specification
|
Input voltage
|
3 x
35000/20230V, star
sine wave
|
|
Transformer
output voltage
|
3 x 690/400V,
star
|
|
Line output
current
|
3 x 1340A,
continuous operating mode
|
|
Frequency
|
50Hz
|
|
Average oil
temperature
|
55°C
|
|
Max. temperature
rise
and/or
max.
Cu-winding losses
at 75°C
|
25°K
18000W => 1.125%
|
|
Short-circuit
voltage
|
6.5%
|
|
°Short-circuit
voltage
|
6.5%
|
|
Max. core losses
|
3200W => 0.2%
|
|
Max. no-load
current
|
1.3%
|
|
Test Voltage at
50Hz, 1 minute
|
Primary 85kV,
outside
Secondary 4kV, inside
|
|
Steel & Core
Assembly |
M5, annealed,
strips for alternated stacking
(4x45°+3x90° per shape),
"round" cross section with 8 steps |
|
Core Size |
Optimized for
minimal material price for:
Cu_Price/Fe_Price = 2
with Cu-winding
|
Creating Input
4 input screens are used to set the input parameters for designing a
transformer:
· Winding parameters
per limb
· Core
· Environment
· Other
and 3 screens for selection and set up of material :
· wires
· steels
· cores.
Criteria and Parameters of Design
The design of a distribution transformer is always framed by 5
criteria which have to be put into effect simultaneously:
·
Short-circuit voltage
·
Winding losses at 75 °C
·
Winding
temperature rise
·
Core
losses
·
No-load
output current
Under this condition the first step is the optimizing the core size to match
the above mentioned prescribed design criteria for the optimal material price
using some additional parameters such as:
·
Cooling media
·
Testing voltages
·
Steel quality and core assembly
·
Winding type and wire type & material
·
Cu/Al and Fe price relationship
Normally the user of this software will create an optimized core
family for a typical design criteria and parameters and select a desired core
per click. In order to demonstrate the procedure for core optimization, note
that the following parameters of optimization are a summery of 5-6 versions:
·
Max. winding losses at 75 °C = 18000W
·
Inductive
short-circuit voltage = 6.4 %
·
Max.
temperature rise 25 °K
For 18000W @ 25 °K you
need a very big cooling surface using the vertical and horizontal
cooling channels in both windings. The optimal windings construction is
presented in the next picture. Note that the secondary winding can be
realized by using foil with 4 cooling channels within the winding and approx.
40% more Cu material for the outside primary winding.

·
Max.
core losses = 3200 W
·
Max,
no-load current = 1.3%
These 2 criteria of design can be easy realized with annealed strips of M111
(M6) grain oriented steel at the induction 1.6T with the following shape and
8 steps "round" cross-section:

·
For 85kV, 50Hz, 1 minute and the
power 1600kVA test voltage the following min. spacing is recommended:

a01=17mm; a12=27mm ;a22=30mm
δ01=δ12=5mm (tubes)
δ22=3mm ; δш=2mm
( 2 x overlaped to increase the creaping
distance to the yoke)
l01=l02=75mm
lц1=lц2=50mm (tube width over the
windings))
Note that the creeping distances between the windings and the HV-winding
and the core have to be bigger than 125mm.
Windings parameters per limb
Primary
The primary is created in star connection. The sine wave input voltage is 20230V .
There are no voltage harmonics and there is no duty cycle operation mode.
The primary will be manufactured with Cu-flat wire in disc winding technology
(view picture above) with the horizontal cooling channel of h=5mm. The advantage
of the disc windings is low voltage per turn without any partial discharging
problems. In order to suppress the high line voltage
discharge the turns of the first and last disc can easily add stronger
insulation.
The following picture describes the manufacturing of a continuous disc
winding:

Secondary
The secondary winding is set inside. It is wound with 2 parallel connected
"bifilar screw" strands (view
picture above). Between each turn there are horizontal cooling channels. h=5mm.
In order to avoid the circulating currents in parallel connected wires per
strand you have to use the transposition through the rotation of the wire
position in the strand in accordance with some rules:

The sine wave output voltage is 399V.
The rms output current is
1336Arms. There are no current harmonics:
Also, there is no duty cycle operation mode on the secondary.
With the eddy current losses factor (RacRdc) 1.4
the number of parallel connected flat wires per strand will be limited . Note that at this point of the design you cannot
prescribe the wire size . You can select only
the wire or family which the program must use in order to select the suitable
wires for your application.

Core
On this input screen you can :
· select and
manipulate the selected steel M97, 030mm (M5l)
· set the
operating induction (1.6T) and the frequency (50Hz)
· select the
core assembly
· and prescribe the core selection out of an input file. This
option will not be used because the core size has to be optimized
.

Environment
The cooling medium is oil with the average
temperature 55°C. The cooling surface of the core is increased
by using 4 L-brackets on the core. The minimum distance between the primary
windings of 2 phases is 30mm. There is no flange but both windings have to be
fixed in order to suppress the axial forces during the short circuit
operation mode.
There is no air in the transformer!

Other...

The selected criteria of the design and core optimization are the winding
losses (18000W => 1.125%) at 75 °C and the inductive short-circuit voltage 6.4%. If
you prescribe also the temperature rise then the program has to use the criterion
which is more critical: either the winding losses or the temperature rise
with the prescribed short circuit voltage.
The core losses and the no-load input current can be manipulated only with
steel quality, core assembly and induction
Core optimization
After you have set all input screens you need to select a core family and
a core as template: 3 phase core family with 8 steps "round" cross
section

Click Core to open the input
screen for reading the parameters of the selected core

Click Optimize to optimize
the core.

The yellow output fields are optimal results. Both other columns have a higher
material price for 2%.
Here you can round off the core diameter (260mm instead 261.1) and click Create. This is the optimized core after
the setting X = Y = 1050 (in order to use only 3 strip sizes per shape).

Output
The first step of the presentation of the output screen is DIAGNOSIS: it
is the summary of the most important calculated parameters of your
transformer.

Note that the program uses the numerical calculation of the magnetic
fields and the temperature rises. Due to this technology the calculations of
the eddy current losses, the steel losses, the short-circuit voltage, the
circulating current and the transposition are very powerful.
The following picture shows the magnetic field outside&inside the core window.


Note that the criterion of design is the
winding losses. With this criterion, the program optimizes the relationship
of the primary and secondary losses. Due to the higher eddy current losses in
the secondary winding and better cooling of the primary winding the
temperature rise of the secondary is higher than
the temperature rise of the primary winding.
A very important detail is the max. oil temperature in the cooling channel
(points 2 ,5, 7 and 10)

Finally here are 4 printed pages showing the design results
Input

Core

Windings
The secondary winding (2 x Scr) is wound with 2
parallel strands. Each strand has 6 parallel flat wires. The transposition
(rotation) of the wires in these 2 strands has to be done after 1., 3.,
5., 7., 9., 11., 13., 15., 17., 19., 21. and 23. turn. The horizontal cooling channel between these 2
strands is 5mm
The calculated number of the discs of the primary winding is 64 discs. In
order to set the -5.0%, -2.5%, +2.5% and +5.0% taps for voltage regulation,
the primary winding is normally cut in the middle. At this point there should be a horizontal
cooling channel 12-15 mm instead 5mm.

Due to high voltage line discharge each turn in the 2 first and the 2
last discs have to be additionally insulated with approx 0.75 - 1.00mm
one-side insulation. For these two reasons, the number of the discs should be set to
62, wound as follows:
·
Discs 1&2 &61&62 => 10
·
28&29&30&31&32&33&34&35
=> 15 turns
·
Other =>20&21 turns

Nominal operating mode

On this page you can check the prescribed parameter:
·
winding losses at 75 °C :0.99%<1.125%
·
short
voltage:6.49% (instead of 6.4%)
·
core
losses:2920W < 3200W
·
No-load
current : 1.2% < 1.3%
·
Max
temperature rise :24.8 °K < 25 °K
·
Max.radial
tension in short-circuit: 18.22N/mm^2 < 60 N/mm^2
·
Max
temp. rises during 4s in short-circuit:59.99°K
Test Mode
If you are not satisfied with the solution made by the program you can
switch into the Test Mode and change your transformer by hand:
· Turns 24.8
· Wire size
· Material (Cu
or Al)
· Number
parallel connected wires and their order in strand
· Cooling
channels and insulations
· Margin
· Steel
· Technology
parameter (impregnation, gaps,...)
and then you can set it under an operation mode changing:
· Input voltage
· Frequency
· Loads and
their K-factors
· Duty cycle of each
winding
· Ambient
temperature
· Air flow

In order to optimize the material costs you need to reduce the very high
eddy current losses. From a material costs point of view, here is a better
version with secondary 2 x 12 flat wires 8mm x 2mm and primary wires 1mm x
8mm in only 48 discs.

Home
|