Designing a 1600kVA/35kV, 50Hz Distribution Oil Transformer
and Oil Tank
General Information
Technical Specification
|
Input voltage
|
3 x 35000/20230V,
star
sine wave
|
|
Transformer
output voltage
|
3 x 400/230V,
star
|
|
Line output
current
|
3 x 2319A,
continuous operating mode
|
|
Frequency
|
50Hz
|
|
Ambient (air)
temperature
and
Min. oil
temperature rise
|
25°C
35°K
|
|
Max. winding
temperature rise
and/or
max.winding losses at 75°C
|
65°K
18000W => 1.125%
|
|
Short-circuit
voltage
|
6.5%
|
|
°Short-circuit
voltage
|
6.5%
|
|
Max. core losses
|
3200W => 0.2%
|
|
Max.
oil temperature rise
at 21200W
|
60°K
|
|
Max. no-load
current
|
1.3%
|
|
Test Voltage at
50Hz, 1 minute
|
Primary 85kV,
outside
Secondary 4kV, inside
|
|
Steel & Core
Assembly
|
30P110,
annealed, strips for alternated stacking
(4x45°+3x90° per shape),
"round" cross section with 8 steps
|
|
Core Size
|
Optimized for
minimal material price for:
Al_Price/Fe_Price = 1
with Al-winding
|
Creating Input
4 input screens are used to set the input parameters for designing a
transformer:
· Winding
parameters per limb
· Core
· Environment
· Other
and 3 screens for selection and set up of material :
· wires
· steels
· cores.
Criteria and Parameters of Design
The design of a distribution transformer is always framed by 5 criteria
which have to be put into effect simultaneously:
·
Short-circuit voltage
·
Winding losses at 75 °C
·
Winding
temperature rise
·
Core
losses
·
No-load
input current
Under this condition the first step is the optimizing the core size to
match the above mentioned prescribed design criteria for the optimal
material price using some additional parameters such as:
·
Cooling media
·
Testing voltages
·
Steel quality and core assembly
·
Winding type and wire type & material
·
Cu/Al and Fe price relationship (per kg)
Normally the user of this software will create an optimized core family for
a typical design criteria and parameters and select a desired core per
click. In order to demonstrate the procedure for core optimization, note
that the following parameters of optimization are a summery of 5-6 designs:
·
Max. winding losses at 75 °C = 18000W
·
Inductive short-circuit voltage = 6.4%
·
Max.winding
temperature rise 65°K at the ambient (air)
temperature 25°
For the
winding losses 18000W with the winding temperature rise to the average oil
temperature of approx. 15-20
°K both windings need to have very
big cooling surface using min.of 3 vertical cooling channels in both windings.
The used windings construction is presented in the next picture. It is
optimal because there is no need for any transposition within the high
current winding and there is no need to worry about the pulse voltage
distribution and partial discharging between the layers within the high
voltage winding

In order to avoid very high circulated losses within a foil winding (max. 5%
is a good value) you need to follow these rules:
- Use Al-foil instead Cu foil.
- In order to reduce the radial magnetic field on the top & bottom of
the foil winding set the distance h > 0 (normally between
15-30mm)
- Increase the distance d between the leg and the first foil
winding
The high voltage winding has to have only 3 layers with 6mm cooling
channel between them. Due to this fact the rectangular wire has to be wound
over the smaller wire side. Normally this winding type has higher
eddy-current losses but using Al-rectangular wire the eddy-current losses
can be easy limited to max 10%
·
Max.
core losses = 3200 W
·
Max,
no-load current = 1.3%
These 2 criteria of design can be easy realized with annealed strips of
30P110 (M110 H,30ZH110, ...) grain oriented steel at the induction 1.75T
with the following shape and 8 steps "round" cross-section:

·
For 85kV, 50Hz, 1 minute high voltage test
and the power 1600kVA the following min. spacing is recommended:

a01=17mm; a12=27mm ;a22=30mm
δ01=δ12=5mm (tubes)
δ22=3mm ; δш=2mm
( 2 x overlapped to increase the
creaping
distance to the yoke)
l01=l02=75mm
lц1=lц2=50mm (tube width over the
windings))
Note that the creeping distances between the HV-windings and the LV-windings
& the core have to be bigger than 125mm.
Windings parameters per limb
Primary
The primary is created in star connection. The sine wave input voltage is 20230V .
There are no voltage harmonics and there is no duty cycle operation mode.
The primary will be manufactured with Al-flat wire in cylindrical
winding technology (view picture above) with 3 vertical cooling
channels of 6mm between 3 layers. The advantage of this winding
configuration is low voltage per turn and no problems with
partial discharging and pulse voltage distribution. In order to
suppress the effect of the high pulse voltage you can
add easely stronger insulation to the10
first and 10 last turns of the winding.
Secondary
The secondary winding is set inside. It is wound with Al-foil and
0.2mm insulation between the turns. In order to increase the cooling surface
the secondary is cut in 3 coils. Between them are 6mm cooling channels. Due to the fact that the first winding to the leg has higher
circulated currents than 2 other coils its number of turns should be smaller
than the number of turns of 2 other coils.
The sine wave output voltage is
230V.
The rms output current is
2319A. There are no current
harmonics.
Also, there is no duty cycle operation mode on the secondary.
With the eddy current losses factor (RacRdc)
1.1 the number of parallel wires & foils will be limited . Note that at this point of the design you cannot
prescribe the wire or foil size . You can
select only the wire family which the program must use in order to select
the suitable wires or foil for your application.

Core
On this input screen you can :
· select and
manipulate the selected steel 30P110 (M 111 H, 30ZH110, 30H110). This
steel has the losses of 1.1W/kg at 1.7T, 50Hz 1nd >1.88T at 800A/m.
· set the
operating induction (1.75T) and the frequency (50Hz)
· select the core
assembly 7 (view the picture above)
· and prescribe the core selection out of an input file. This
option will not be used because the core size has to be
optimized by program.

Environment
The ambient (air) temperature is 25°C
The cooling medium is oil with the minimum oil temperature
rise on the oil tank bottom of 35°K Note that this temperature rise
has to be fine-tuned during the oil tank design in the Test Mode..
The cooling surface of the core is increased by using 4 L-brackets on the
core. The minimum distance between the primary outside coils of 2 phases is
30mm. There is no flange but both windings have to be fixed in order to
suppress the axial forces during the short circuit operation mode.
There is no air in the windings nor the gaps between the windings and
insulations!

Other
Here you can set the criteria for design (winding temperature rise
or winding losses at any temperature) and/or the criteria for optimization
for the minimum of the material price.

The selected criteria of the design and core optimization are the winding
losses (18000W => 1.125%) at 75
°C and the inductive short-circuit voltage 6.4%.
Note that the program can NOT optimize (but it can calculate) the
losses of the circulated current in the foil changing winding material and
spacing because this has to be set by designer only. Due to this fact
the prescribed windings losses are set to 1.05% instead 1.125%
If you prescribe also the winding temperature rise then the program has
to use the criterion which is more critical: either the winding losses or
the winding temperature rise with the prescribed inductive short circuit
voltage.
The core losses and the no-load input current can be manipulated only with
steel quality, core assembly and induction
If the ratio of the price per kg between the windings and core material
is 1 then the transformer is optimized for minimum price and weight.
Core optimization
After you have set all input screens you need to select a core family and a
core as template: 3 phase core family with 8 steps "round" cross section

Click Core to open the input
screen for reading the parameters of the selected core

Click Optimize to optimize the
core.

The yellow output fields are optimal results. Both other columns have a
higher material price for 2%.
At this point you have to check whether the active and reactive core
losses are within the prescribed range:
Active core losses = 2175W < 3200W
Reactive core losses = 16803VAr = 1.05% < 1.3%
The next check what the effect of the radial mechanical forces are during the short-circuit operation mode:(7.33 N/mm2 < 25 N/mm2, max. allowed for
Al) and the average winding temperature rise to the average oil temperature
(5.962°K < 15°K)
Here you can round off the core diameter (213mm instead 212.8) and
click Create. This is the optimized core .

Output
The first step of the presentation of the output screen is DIAGNOSIS: it is
the summary of the most important calculated parameters of your transformer.
Windings losses at 75°C Uccr = 1.1% < 1.125%
Inductive short-circuit voltage Uccx = 6.21% <> 6.4%
Winding temperature rise to the ambient (air) temperature is 56°K < 65°K

The second very important output screen is the Test Mode. In this program
part the transformer can be manually fine-tuned and redesigned.
First you need to round off the number of turns. Then to set equal foil
thickness for 3 secondary coils and finely to select by hand a rectangular
wire (wound over the smaller wire side) to get one full layer per each primary
coil.

Here is the finally result

Here are some remarks to this design:
- Very simple winding construction.
- Winding losses 17604W < 18000W
- Reactive short-circuit voltage 6.3% < 6.4%
- Windings temperature rise 53°K < 65°K
- Max. oil temperature rise 55°K < 60°K
- Core losses 2134W < 3200W
- Reactive core losses 16092 = 1% < 1.3%
Here are 4 printed pages with all input and output parameters of the
transformer
Page 1

Page 2

Page 3

Page 4

Oil Tank
During the transformer design the minimum oil temperature rise on the
bottom of the oil tank (common for all windings) was set to 35°K. The
calculated transformer and oil temperatures are presented in the following
diagram:

Legend:
- 1 => Core
- 2,5,7,9,11,14,16,18 => average oil temperature in the cooling
channels
- 3,4,12,13 => surface of the insulation
- 6,8,10,15,17,19 => average winding temperature
Note that the program calculates the max. oil temperature and the oil
flow (the
amount per second) in the cooling channels and the max. oil temperature on the
top of the oil tank as the average value of the mixed amounts of the oil
on the exits of the cooling channels.
In this case the max. oil tank temperature is 80.58°C (the temperature rise
55.58°K<60°K)
From thermal point of view the program supports the following
8 types of oil tank cooling:
cooling:
In the first step you need to set the size of the "naked"
oil tank. For your reference the dimensions of the calculated transformer are
presented on the top of the input screen. The result of your settings in
this input frame are the oil tank dimensions, the amount of the oil and the
max. oil temperature rise of the "naked" tank. Note that the amount of
the oil is calculated without the coolers (fins, tubes and radiators).

The next step is the setting of the cooler. In this case the selected cooler is with cooling fins

After you set the size of the cooling fins the program will calculate the
max. available number of the fins and the max. oil temperature rise. You can change
the fin size or reduce the number of fins in order to get max. oil
temperature rise approx 55.58°K. If you set the max. oil temperature rise at
60°K (changing the cooling fins) then you need to redesign the
transformer with the min. oil temperature rise 39.42°K (instead 35°K).
Circulated Current Losses
Note that the program uses the numerical calculation of the magnetic
fields. Due to this technology the calculations of the circulated current
losses is very powerful.
The following pictures show the magnetic field
inside of the core window by the margin of the secondary
winding 75mm and 45mm. You can see that the radial magnetic field
through the top of the secondary winding is stronger with the margin
75mm and the circulated current losses higher:
- The primary margin=75mm, the secondary margin=75mm => the circulated
current losses = 1300W/phase
- .
- The primary margin=75mm, the secondary margin=45mm => the circulated
current losses = 220W/phase

Eddy current losses
Due to high voltage line discharge and for a good pulse voltage
distribution the first & last 10 turns have to be additionally insulated with approx 0.75 - 1.00mm
insulation.
From the manufacturing point of view is the primary winding construction
optimal but from eddy current losses point of view it is only a "good"
compromise: 13% (instead 2-3%) more losses in the primary winding
Radial Tension
Normally the Al foil winding is more sensitive to the mechanical
forces in the short-circuit operation mode. Max. allowed tension in the
cross section of a Al wire or Al foil is 25 N/mm2. In our design example the
max. tension is 11.73 N/mm2
Winding temperature rise in the short-circuit operation mode
The max. winding temperature rise in the short circuit operation mode
after 4 seconds is 52.44°K. The max. winding temperature after the short
circuit operation mode out of the nominal operation mode will be
25+54.2+52.44 = 131.64°C
|