Title |
Three-Phase LC-Resonance Filter Choke, connected in series with capacitor
|
|
Input |
· Set inductance at peak current (View the peak value on the current diagram). The resonance frequency is 189Hz for Ul/Uc=7% · Select the AC inductance : L-Type = 1 · Select Cu round wire: Wire = 0 · The frequency of the first harmonic is 50Hz · Set the rms values of harmonics of the thermal current. These harmonics have to be prescribed by your customer! · Set the temperature rise · Select grain oriented steel. Note that the induction will be optimized by program in order to get optimal relationship between core losses and winding losses · Set Gap = 1 and Core Assembly = 2 or better · Select suitable 3 phase core family. If there are 3. and 9. harmonics (circuit c) then you need to use 3 one phase cores. |

|
Output |
· Control the value of induction, gap and connected wires in parallel |
|
Test |
· Round the number of turns |
|
Note |
· In order to calibrate the choke, connect it on the calculated calibration 3 phase AC-voltages (rms value) with the calibration frequency (normally 50Hz or 60Hz) and then vary the gap until you get the calculated calibration 3 phase AC-current (rms value). |