How do we design
a rectifier safety transformer for feed to voltage controllers of
5Vdc,1Adc and 2x12Vdc,0.1Adc with RC-loadin accordance with IEC 61558 ?
Technical specification relevant only
to design
Electrical data and diagram
Input voltage |
: 230V, +6%, -10%,
sinusoidal |
Frequency |
: 50Hz |
Min. output voltage 1 |
: 8Vdc, at -10% of input
voltage |
Nominal output voltage 1 |
: max.14Vdc, at +6% of input
voltage |
Nominal output current 1 |
: 1Adc, RC load |
Min. output voltage 2 |
: 2x15Vdc, at -10% of input
voltage |
No-load output voltage 2 |
: max. 2x25dc, at +6% of
input voltage |
Nominal output curren 2 |
: 0.1Adc, RC load |
Voltage ripple |
: max 5% |
Ambient and operating conditions:
max. 2x25dc, at
+6% of input voltage |
40°C |
Mode of operation |
Continuous, for
5V and 2x12V voltage controller feed |
Test conditions |
Not
short-circuit proof transformer |
Specification
- Safety transformer as per IEC 61558
- Insulation class E
Criteria for design
IEC 61558
A transformer which is not required by IEC 61558 to be
short-circuit proof is manufactured without protection. However,
the manufacturer is obliged to inform the user of the required
safety precautions by means of which the transformer must be
protected in operation. In this case, the transformer must be
protected by means of a miniature fuse as per IEC 127: the type
and nominal current of the fuse must be stated on the
transformer's information label.
The procedure for testing is prescribed as follows in
accordance with paragraphs 14.2 and 15.3.3:
- Firstly, the transformer is loaded in accordance with
paragraph 14.2 with the nominal load resistance and at
1.06 x the nominal input voltage until permanent
operating temperature is achieved. In this context, the
temperature of the windings must not exceed the value of q nominal.
- Immediately after this test, in accordance with paragraph
15.3.3, all secondaries are loaded at K x the nominal
current of the fuse for time period T. Time period T is
the longest pre-arcing period of the fuse, caused by K x
the nominal current of the fuse. After lapse of time
period T, the temperature of the windings must not exceed
the value of q max. The
typical values for a slow-blow fine fuse as per IEC 127
are:
T = 30 minutes
K = 2.1
Here, the temperature of the windings must not exceed q max and that of the case
must not exceed the values set out on the following
table.
In the case of transformers with regulation greater than
20%, switch-on current is not a criterion for our choice
of fuse. Consequently, we can select a rapid fuse, which
will result in a much shorter pre-arcing time.
- Finally, all output windings are short-circuited. at 1.06
x the nominal input voltage, the integral thermal cutout
should actuate, before the temperature exceeds the value
of q max as per the
following table:
Insulation
class |
A
|
E
|
B
|
F
|
H
|
Typical
pre-arcing time T (in minutes) |
30
|
30
|
30
|
30
|
30
|
Typical
factor K |
2.1
|
2.1
|
2.1
|
2.1
|
2.1
|
Max winding
temperature
in test q max (° C) |
200
|
215
|
225
|
240
|
260
|
Max winding
temperature
in nominal operation mode q nominal (° C) |
100
|
115
|
120
|
140
|
165
|
Insulation class
Max winding temperature in nominal operation mode = 115°C
Max winding temperature in test mode = 215°C
Insulation class E is prescribed.
Output voltage
A rectifier transformer with RC load, for which the minimum
and maximum output voltages are described, must adhere to the
prescribed tolerances. For that reason, the transformer is
firstly designed in accordance with the criterion of regulation
(criterion = 1) and then tested to IEC in the test program.
Rectifier transformers with RC load can only be designed in
accordance with the criterion regulation.
The output voltages of 2x15Vdc are grouped together as one
single voltage of 30Vdc and calculated as the output voltage of a
shunt rectifier. After our design work, we must provide for a tap
in the middle of the calculated number of windings. If the
designed value amounts to that of capacity C, then connectors C21
and C22 must have the value of 2*C.
Regulation (voltage boosting)
For purposes of designing the transformer in accordance with
the regulation criterion (voltage boosting), we have to
enter the value for boosting the voltage of the secondary
voltages. Regulation is calculated as follows by means of the
direct current voltages:
The transformer is designed for 207Vac. In this context, the
output voltages under load in the hot state must not fall short
of the values of 8Vdc and 2x15Vdc. The maximum no-load voltages
must not exceed the levels of 14Vdc and 2x25Vac at an input
voltage of 243.8Vac. At an input voltage of 207Vac, the no-load
voltages should be below the levels of 14*207/243.8=11.9Vdc and
2x21.2Vdc. This corresponds to a regulation of the output voltage
of 100*(11.9-8)/8=<50%. The increase in the secondary voltages
(regulation) should be a maximum of < 20-25% as per the
following table.
Regulation of secondary voltage
%
|
Regulation of the DC voltage of a single-phase
shunt rectifier with RC load
%
|
Regulation of the DC voltage of a triple-phase
shunt rectifier with RC load
%
|
1
|
8-12
|
5-6
|
2.5
|
12-14
|
7-8
|
5
|
14-17
|
9-10
|
10
|
20-25
|
13-14
|
15
|
30-33
|
17-18
|
20
|
37-40
|
20-22
|
30
|
52-54
|
30-32
|
40
|
64-66
|
41-43
|
50
|
80-82
|
50-53
|
Output voltage ripple
Output voltage ripple can be prescribed as follows:
Ripple = 100*(Udcmax-Udcmin)/(Udcmax+Udcmin)
The program calculates the magnitude of the required
capacity of the smoothing condensers for the prescribed DC
voltage ripples.
Bobbin unit
Is this performance range, recourse is had almost exclusively
to a double-chamber bobbin unit.
Lets choose a double-chamber bobbin unit .
Impregnation
The bobbin unit or the window of the core is injected under
pressure. In this method, we save on the quantity of potting
compound with the same voltage resistance as a potted
transformer, and we don't need a case.
The winding space of our transformer is injected under
pressure. The windings are pressed.
Induction
We select our induction on the basis of a voltage level below
the input voltage of -10%, between 1.2 and 1.4.
Procedure for design
- If you are not yet acquainted with Rale Design software,
please read the text: "How do I design a small
transformer?". You should keep a copy of this
text within your reach whenever performing design
operations.
- Fill out the input mask as follows. If you need any help,
press function key F1. There is extensive description for
each box.
- The input field selection contains a value
`0. This means that the program should search
on-line for a suitable core for this application, from
your choice of core family.
- Save your input data file. In this design example, the
input data was saved in input data CAL0005E.TK1.
This input data file was supplied together with this
document.. Copy it into the directory in which the Rale
demo program is installed.
- Connect up to the Rale design server.
- Load up your input data file.
- Now choose the core family from which you want to look
for a suitable core for your application. Ensure that the
marked core is AUTO.
- Click on OK.
- Start your design work. The core is selected
automatically from your prescribed core family, and the
program offers you a core, which is sized adequately for
your application. Click on OK in order to accept the
core.
On completion of your design work, the following design data
is available and can be printed on three pages:
This is followed by checking of the design data.
- Firstly, we check the DC output voltages: 8.3Vdc and
30.2Vdc
- Then we check the winding data and the filling factor
(96.8%<100%).
- This is followed by the IEC 61558 test: since the voltage
controller has a current limiter, the output currents of
the transformer are also limited, for practical purposes:
max 1.5A and 0.15A. For that reason, we select slow-blow
fuses with nominal currents of 1.5A and 0.15A.
dT = 40 + 117.6°K = 157.6°K < 215°K : OK
This is followed by testing at the input voltage of 243.8V:
U in = 1 * 243.8/207 = 1.18 page of the data sheet for the
winding, we should check up on the no-load output voltage:
13.5Vdc<14Vdc and 47.7Vdc<50Vdc is not satisfactory, then
There are two means of implementing the desired correction:
- We can either return to the input mask (function key F2),
correct the input data and re-design the transformer,
- Or we can access the test program (function key F5),
modify the transformer design manually and change the
transformer design by that means.
On completion of our design work, we can print out the design
data on-line, or save it on the local PC and print it out
off-line. The output data file from this design example,
CAL0005G.TK2, was supplied together with this document. Copy it
into the directory in which the Rale demo program is installed.
Tips & Tricks
The temperature in the nominal operating mode is too high
- Reduce your regulation and increase your induction.
- Select a better core quality.
- Increase your cooling surface area.
Adapter
This type of transformer is very often employed in a case, not
potted, as an adapter
Smoothing condenser
The program has calculated the following values for the
prescribed DC voltage ripple:
C1 >= 6500µF
C21 = C22 = 2 * 171µF =>360µF
A double-chamber transformer requires a lower capacity than a
single-chamber transformer for the same output voltage ripple. |